FP Air Cooled Hazardous Area Air Conditioning Unit

Product code FP12 FP18 FP24
Nominal Cooling Load (kW) 3.50 5.25 7.00
Nominal Air Flow - low (m³/h) 400 500 800
Nominal Air Flow - high (m³/h) 500 675 1000
Evap. Fan motor rating (kW) 0.037 0.045 0.074
Comp. Motor Power (kW) 1.87 2.28 2.89
Cond. Fan motor rating (kW) 0.18 0.25 2@0.18
Internal Unit Dimensions - H (mm) 450 550 550
Internal Unit Dimensions - W (mm) 760 760 1060
Internal Unit Dimensions - D (mm) 380 380 380
Unit Weight (kg) 125 135 195
Electric Heating (Optional) (kW) 1.5 1.5 3.0

Nominal duties are based on air entering @ 25°Cdb @ 50% RH utilising R407c and ambient air @ 40°C

  • Nominal cooling loads 3.5 kW, 5.25 kW and 7.0 kW
  • Air Cooled
  • Refrigerant R407c / R449A / R448A
  • A60 class fire resistant division between internal and external section
  • Internal section
    • Suitable for non-hazardous area
    • Electro coated mild steel casing with powder coated paint finish RAL 9018 (Grey)
  • External section
    • ATEX II 2 G EEx d IIB T4 suitable for hazardous area
    • Cu/Cu condenser coil
    • Stainless steel 316 casing with 2 component Polyurethane paint finish RAL 9018 (Grey)
  • Removable top and side panels for access and maintenance
  • Quick release grille for air filter cleaning and replacement
  • Close coupled units supplied factory precharged
  • Electrical supply
    • 220V 1ph 50/60Hz
    • 380V 3ph 50Hz
    • 440V 3ph 60Hz
  • Other options available
    • Colour to suit operating environment
    • Split system version
    • Electric heating
    • Refrigerant R134a