FP Air Cooled Hazardous Area Air Conditioning Unit
Product code | FP12 | FP18 | FP24 |
Nominal Cooling Load (kW) | 3.50 | 5.25 | 7.00 |
Nominal Air Flow - low (m³/h) | 400 | 500 | 800 |
Nominal Air Flow - high (m³/h) | 500 | 675 | 1000 |
Evap. Fan motor rating (kW) | 0.037 | 0.045 | 0.074 |
Comp. Motor Power (kW) | 1.87 | 2.28 | 2.89 |
Cond. Fan motor rating (kW) | 0.18 | 0.25 | 2@0.18 |
Internal Unit Dimensions - H (mm) | 450 | 550 | 550 |
Internal Unit Dimensions - W (mm) | 760 | 760 | 1060 |
Internal Unit Dimensions - D (mm) | 380 | 380 | 380 |
Unit Weight (kg) | 125 | 135 | 195 |
Electric Heating (Optional) (kW) | 1.5 | 1.5 | 3.0 |
Nominal duties are based on air entering @ 25°Cdb @ 50% RH utilising R407c and ambient air @ 40°C
- Nominal cooling loads 3.5 kW, 5.25 kW and 7.0 kW
- Air Cooled
- Refrigerant R407c / R449A / R448A
- A60 class fire resistant division between internal and external section
- Internal section
- Suitable for non-hazardous area
- Electro coated mild steel casing with powder coated paint finish RAL 9018 (Grey)
- External section
- ATEX II 2 G EEx d IIB T4 suitable for hazardous area
- Cu/Cu condenser coil
- Stainless steel 316 casing with 2 component Polyurethane paint finish RAL 9018 (Grey)
- Removable top and side panels for access and maintenance
- Quick release grille for air filter cleaning and replacement
- Close coupled units supplied factory precharged
- Electrical supply
- 220V 1ph 50/60Hz
- 380V 3ph 50Hz
- 440V 3ph 60Hz
- Other options available
- Colour to suit operating environment
- Split system version
- Electric heating
- Refrigerant R134a