Fan Coil Air Conditioning Unit

Product code FC10 FC15 FC20 FC25 FC30 FC40 FC50 FC70
Nominal Cooling Load (kW) 10 15 20 25 30 40 50 70
Nominal Air Flow (m³/h) 1600 2600 3600 4500 4800 6300 8000 11250
Nominal Water Flow (l/s) 0.4 0.6 0.79 1.0 1.19 1.59 1.98 2.78
Pressure drop (kPa) 41 47 47 48 49 48 50 49
Fan Motor Rating (kW) 0.37 0.55 0.75 1.10 1.10 1.50 1.50 2.20
Unit Dimensions - H (mm) 1500 1750 1750 1750 1750 1750 2000 2000
Unit Dimensions - W (mm) 500 700 700 700 700 1200 1200 1500
Unit Dimensions - D (mm) 500 750 750 750 750 750 750 750
Unit Dimensions - P (mm) 260 270 330 340 340 340 400 450
Unit Weight (kg) 121 168 185 205 221 278 303 372
Electric Heating (Optional) (kW) 4.5 9 12 12 12 18 18 18

Nominal duties are based on air entering @ 25°Cdb @ 50% and CW 6°C – 12°C

  • Normal Cooling loads 10 kW to 70 kW
  • Duct connection
  • Electro coated mild steel casing with powder coated paint finish RAL 9018 (Grey)
  • Removable front panels for access and maintenance
  • Quick release grille for air filter cleaning and replacement
  • Electric supply 380V 3ph 50Hz, 440V 3ph 60Hz, 220V/1ph/50Hz, 230V/1ph/60Hz
  • Other options available
    • Plenum and Grille discharge
    • Controls pack including:-
      • Built in 3 way valves
      • Actuators
      • Control unit
      • Thermostatically controlled
      • Set point adjuster on front of unit
    • Colour to suit operating environment
    • Alternative fan pressures
    • Electric or hot water Heating
    • Fresh air connection
    • Stainless steel casing