KWG Galley Self Contained Air Conditioning Unit
Product code | KWG10 | KWG15 | KWG20 | KWG25 |
Nominal Cooling Load (kW) | 10 | 15 | 20 | 25 |
Nominal Heating Load (kW) | 9.0 | 12.0 | 13.5 | 18.0 |
Nominal Air Flow (m³/h) | 600 | 700 | 1100 | 1550 |
External Pressure (kW) | 600 | 600 | 600 | 600 |
Fan Motor Rating (kW) | 0.37 | 0.37 | 0.55 | 0.75 |
Comp. Motor Power (kW) | 3.55 | 4.72 | 6.45 | 9.79 |
Nominal Water qty. (m³/h) | 1.08 | 1.56 | 3.12 | 3.70 |
Unit Dimensions - H (mm) | 1500 | 1750 | 1750 | 1750 |
Unit Dimensions - W (mm) | 550 | 700 | 700 | 700 |
Unit Dimensions - D (mm) | 550 | 750 | 750 | 750 |
Unit Weight (kg) | 230 | 320 | 340 | 370 |
Nominal duties are based on 100% fresh air entering @ 35°Cdb @ 70% RH (Summer) and -25°C (Winter) utilising R407c with fresh water @ 36°C
- Unit designed to meet SOLAS 2000 requirement
- Nominal cooling loads 10.0 kW to 25.0 kW
- Fresh water cooled through plate heat exchanger
- Refrigerant R407C / R449A / R448A
- Ducted, filtered rear inlet and vertical discharge
- Electro coated mild steel casing with powder coated paint finish RAL 9018 (Grey)
- Removable panels for access and maintenance
- Units supplied factory precharged only requiring suitable water and electrical connections
- Electrical supply 380V 3ph 50Hz or 440V 3ph 60Hz
- Electric heating
- Other options available
- Stainless steel 316 casing with powder coated paint finish RAL 9018 (Grey)
- Colour to suit operating environment
- Alternative fan pressures
- Split system version
- Hot water heating
- Refrigerant R134a or R404A
- Air cooled